JourneymanIQ
Calculator · NEC 314.16

Box fill.

Count the conductors. Each yoke is two of the largest in the box. All grounds together count as one. Internal clamps add one of the largest. Then compare against Table 314.16(A) volume.

Conductors by AWG
Required volume0.00 cu in
Box volume21.00 cu in

The box has room. You are clear.