Voltage Drop Calculator: How to Use It (and When It Lies)
Voltage drop isn't an enforceable NEC rule for branch circuits. It's an informational note. But it shows up on exams and on every real installation that runs more than 100 feet. Here's how to do it by hand, when to trust the calculator, and the three traps that catch most candidates.
Last reviewed May 2026
The formula
For single-phase, two-wire circuits:
Vd = (2 × K × I × L) / Cmils
For three-phase circuits, replace the 2 with √3 (1.732):
Vd = (1.732 × K × I × L) / Cmils
The inputs
- K: resistivity constant. Copper = 12.9. Aluminum = 21.2. Approximations; actual K varies slightly with temperature.
- I: current in amperes. Use the actual operating current, not the OCPD rating.
- L: length of the run in feet, one way. The 2 (or 1.732) handles the round trip.
- Cmils: circular mils of the conductor. From Chapter 9 Table 8. 14 AWG = 4,110 cmils. 12 AWG = 6,530. 10 AWG = 10,380. 8 AWG = 16,510. 6 AWG = 26,240. 4 AWG = 41,740. Memorize the common ones.
What the NEC actually says about voltage drop
The NEC has informational notes (not enforceable) suggesting:
- Branch circuits: voltage drop should not exceed 3% (NEC 210.19 informational note 4).
- Combined branch + feeder: should not exceed 5% (NEC 215.2 informational note 2).
- Sensitive electronic equipment: tighter limits, vendor-specific.
Informational notes are not code. The exam will still ask you to apply them. On the job, voltage drop becomes a code issue when it’s linked to ampacity correction or when local amendments make it enforceable.
A worked example
Single-phase 120V circuit, 12 AWG copper, 100 ft, 16 A continuous load.
- K = 12.9 (copper)
- I = 16 A
- L = 100 ft
- Cmils = 6,530 (12 AWG)
- Vd = (2 × 12.9 × 16 × 100) / 6530 = 41,280 / 6530 ≈ 6.32 V
- % drop = 6.32 / 120 = 5.3%
That’s above the 3% target. Remedies: bigger conductor (10 AWG drops it to 3.3%), shorter run, or accept the drop if the equipment tolerates it.
Three traps that catch candidates
Trap 1: Confusing OCPD rating with operating current
The voltage drop formula uses the actual current, not the breaker size. A 20A breaker on a circuit pulling 12 A draws based on the 12 A. The exam may mention both, so read carefully.
Trap 2: Forgetting the round trip
Single-phase voltage drop counts both legs (the 2 in the formula). Some candidates calculate one-way and report half the actual drop. Verify that your formula accounts for the round trip.
Trap 3: Single-phase vs three-phase coefficient
Use 2 for single-phase, 1.732 (â3) for three-phase. Don’t use 2 for three-phase or vice versa. The coefficient embeds the phase relationship in the math.
When the calculator is right but the answer is wrong
A calculator gives you a number. It doesn’t tell you whether the number is acceptable. Two scenarios where the math passes but the install fails:
- The 3% target is informational. If your job specs require 2%, the calculator’s 'OK' isn’t.
- Voltage drop on the start-up surge of a motor can be much higher than at running current. Sizing for running current alone undersizes for inrush.
Drill voltage drop on real exam questions
The diagnostic includes calculation problems across all five common types: voltage drop, conduit fill, box fill, motor sizing, and dwelling load.