Motor FLA, Branch Circuit, and OCPD Sizing for Electricians
Article 430 has more percentages than any other NEC article. 125%, 115%, 175%, 250%, 800%. Each one applies to a different sizing decision. Memorize the rule, not just the number.
Last reviewed May 2026
The first rule: FLC vs FLA
Two terms that sound similar but aren’t:
- FLC: Full Load Current. From NEC Tables 430.247-250 (DC, single-phase, three-phase, two-phase). Used for branch-circuit conductor sizing and short-circuit/ground-fault protection.
- FLA: Full Load Amps. Read off the motor nameplate. Used for overload protection.
This split is the single most common motor-question trap. The exam will ask for branch-circuit conductor size (FLC from the table) and the very next question will ask for overload (FLA from the nameplate). If you mix them up, both answers go wrong.
Branch-circuit conductors: 125%
Per 430.22, branch-circuit conductors for a single continuous-duty motor must have an ampacity of at least 125% of the motor’s FLC (from the table, not nameplate).
Example: 25 HP, 460V, three-phase squirrel-cage motor. Table 430.250 → 34 A FLC. Branch-circuit conductor ampacity = 34 × 1.25 = 42.5 A. Pick the next standard wire size with that ampacity.
Overload protection: 115% or 125%
Per 430.32(A)(1), overload protection is sized from the motor nameplate FLA:
- Service factor 1.15 or greater → 125% of nameplate FLA
- Temperature rise 40°C or less → 125% of nameplate FLA
- All other motors → 115% of nameplate FLA
Example: Motor with nameplate FLA of 28 A and SF of 1.15. Overload max setting = 28 × 1.25 = 35 A. Note: this uses 1.25, the SF-1.15 percentage. Common trap: candidates use 1.15 because the SF is 1.15. The percentage and the SF aren’t the same number.
Short-circuit and ground-fault protection: 175% to 800%
Per Table 430.52, the SCGF device (the upstream branch breaker or fuse) is sized as a percentage of the FLC. The percentages vary by motor type and protection device:
- Inverse-time circuit breaker, three-phase squirrel-cage motor → 250% of FLC
- Non-time-delay fuse, same motor → 300% of FLC
- Time-delay fuse, same motor → 175% of FLC
- Instantaneous-trip breaker, same motor → 800% of FLC (with engineering supervision)
The percentages stack: SCGF protection lets a much higher current pass than the conductor ampacity, because the device’s real job is to trip on a short circuit (thousands of amps), not on motor overload (handled separately).
Feeder conductors for multiple motors: 125% of largest, 100% of others
Per 430.24, when one feeder serves multiple motors, the conductor ampacity must be at least 125% of the largest motor’s FLC plus the sum of the other motors’ FLC at 100%.
Common motor traps
- Mixing FLC (table) with FLA (nameplate). The exam writes scenarios where both numbers are given. Read which one the question wants.
- Using 1.15 instead of 1.25 for service factor 1.15 motors. The SF determines which row of 430.32 applies, not the percentage itself.
- Forgetting that 430.52 percentages apply to FLC from the table, not to nameplate FLA.
- Treating the inverse-time breaker the same as the non-time-delay fuse. They have different percentages.
Drill motor sizing on real exam questions
The diagnostic includes motor problems across all four sizing decisions: branch circuit, overload, SCGF, and feeder.