NEC Box Fill Calculations
Box fill is not hard because the arithmetic is hard. It is hard because the exam hides the count. Get the count wrong and the calculator gives you a clean wrong answer.
Last reviewed July 2026
The rule family
Box fill lives in NEC 314.16. The setup is simple once you stop treating it like a random math problem. You are not solving for a mystery formula. You are asking one question: how many conductor allowances are inside this box?
If you want the number checked after you count it, use the free box fill calculator. If you are sitting for the exam, learn the count first. That is where the points are lost.
The count that actually matters
- Each conductor that enters the box and is spliced, terminated, or passes through counts as one allowance.
- A pigtail that starts and ends inside the box does not count.
- Each device yoke counts as two allowances based on the largest conductor connected to it.
- All equipment grounding conductors together count as one allowance.
- An internal cable clamp counts as one allowance. An external clamp does not take box volume the same way.
- A support fitting inside the box counts as one allowance.
Common Table 314.16(B) values
These are the values most exam questions use. Confirm the exact row in your own NEC on test day.
- 14 AWG: 2.0 cubic inches
- 12 AWG: 2.25 cubic inches
- 10 AWG: 2.5 cubic inches
- 8 AWG: 3.0 cubic inches
- 6 AWG: 5.0 cubic inches
Worked example: 4 in. square box with one receptacle
A 4 in. square box has 21.0 cubic inches marked. Inside the box are four 12 AWG insulated conductors, one duplex receptacle on one yoke, two 12 AWG equipment grounding conductors, and one internal clamp. Is the box large enough?
- Insulated conductors: 4 allowances x 2.25 = 9.00 cubic inches.
- Device yoke: 2 allowances x 2.25 = 4.50 cubic inches.
- Equipment grounds: 1 allowance x 2.25 = 2.25 cubic inches.
- Internal clamp: 1 allowance x 2.25 = 2.25 cubic inches.
- Total required volume: 18.00 cubic inches.
- Box volume: 21.00 cubic inches. The box is large enough.
Wrong answers the exam wants you to pick
Counting every ground
Five grounds still count as one allowance. The count is based on the largest equipment grounding conductor in the box.
Forgetting the yoke
A yoke counts as two allowances. This is the detail that makes a box pass or fail in many device-box questions.
Counting pigtails
A pigtail starts and ends inside the same box. It does not enter from outside the box, so it does not add a box-fill allowance.
How to drill this for the exam
Run the count without a calculator first. Say the categories out loud: conductors, yokes, grounds, clamps. Then use the calculator to check the cubic inches. If your miss keeps coming from the count, more arithmetic will not fix it. You need more box-fill reps.
Find out if box fill is actually your weak spot
The free diagnostic shows whether box fill, conduit fill, motors, grounding, or another NEC area is costing points.