NEC Article 250 Lookup Practice (California Electrician Exam)
Article 250 is long, and candidates lose minutes wandering it. The fix is a map: know which section and table answers a grounding question before you open the book.
Last reviewed June 2026
What to train
- The split between the electrode conductor (250.66, off the service) and the equipment ground (250.122, off the breaker).
- Reading Table 250.66 by the largest ungrounded service conductor.
- Reading Table 250.122 by the overcurrent device rating.
- Where bonding lives: 250.102 jumpers, 250.104 water pipe and building steel.
What slows candidates down
- Confusing the two tables and sizing the equipment ground off the service conductor.
- Searching 'ground wire' instead of the defined terms in the index.
- Reading Article 250 from the top instead of jumping to the Part you need.
- Missing that the main bonding jumper has its own section.
Mini drill: find it fast
Close the book. Read each cue, say the index keyword you would search and the article out loud, then check yourself. If it takes more than fifteen seconds, that one goes on your tab list.
Size the grounding electrode conductor
Sized by the largest service-entrance conductor.
Keyword: Grounding electrode conductor
Table 250.66
Size the equipment grounding conductor
Sized by the overcurrent device ahead of it.
Keyword: Equipment grounding conductor
Table 250.122
Supply-side bonding jumper
Sized from Table 250.102(C)(1).
Keyword: Bonding jumper, supply-side
250.102(C)
Ground rod electrode requirement
Rod electrodes and their installation.
Keyword: Grounding electrode, rod
250.52 and 250.53
Main bonding jumper at the service
Ties the neutral to the enclosure at the service.
Keyword: Bonding jumper, main
250.28
Train this against the clock
Check every domain in 15 minutes.
Drill this topic, then run the diagnostic to see if anything else is leaking points on the California General Electrician exam. Free, no signup.
Take the free diagnostic