Grounding and Bonding Practice for the California Exam
Two different tables. The grounding electrode conductor sizes off the service conductors (250.66). The equipment grounding conductor sizes off the breaker (250.122). On the California exam, calculations are part of the Determination of electrical system requirements domain. Here is the pattern, one worked example, and a question to try.
Last reviewed June 2026
One worked example
A service with 3/0 copper service-entrance conductors. Size the grounding electrode conductor.
- 1Name the problem
Grounding electrode conductor, so Table 250.66, sized off the service conductors.
- 2Pick the rule
Table 250.66 takes you from the service-conductor size to the GEC size.
GEC ← Table 250.66 (service size)
- 3Pull the numbers
Service is 3/0 copper.
- 4Run the arithmetic
Read across Table 250.66. 2/0 through 3/0 copper service lands on a 4 AWG copper GEC.
3/0 Cu service → 4 AWG Cu GEC
- 5Check it
4 AWG copper. Different table than the EGC, do not grab 250.122 by mistake.
Now try one
Your turn. A branch circuit protected by a 60-amp breaker.
Using Table 250.122, what copper equipment grounding conductor does it need? Enter the AWG number.
- 1Run the arithmetic
Read Table 250.122. A 60-amp circuit calls for a 10 AWG copper EGC.
60 A → 10 AWG Cu EGC
- 2Check it
10 AWG copper. The breaker drives the EGC, the service drives the GEC.