JourneymanIQ
Washington · practice

Washington grounding and bonding practice questions

Grounding and bonding is one of the topics that shows up most in the NEC and theory section of the Washington general journeyman (01) exam. It is open book on the 2020 NEC, but the answer being in the book does not help if you grab the wrong row or miss the exception. Here is the rule that governs it, a clean worked example, and where to practice it under time.

Last reviewed June 2026

What grounding and bonding is asking you

A grounding and bonding question gives you a service or feeder and asks for the right conductor: the grounding electrode conductor that ties the system to the electrodes, or the equipment grounding conductor that bonds the metal back to the source. The most common version on the exam is sizing the grounding electrode conductor, and the governing rule is NEC Table 250.66. That table maps the size of the largest ungrounded service-entrance conductor to the required grounding electrode conductor.

  • Grounding electrode conductor: sized from NEC Table 250.66 against the largest service conductor.
  • Ground rod exception, 250.66(A): a conductor run only to a made electrode such as a ground rod never has to be larger than 6 AWG copper.
  • Equipment grounding conductor: sized from NEC Table 250.122 against the overcurrent device, a separate table you do not want to confuse with 250.66.

The trap is which table you reach for and which exception applies. The grounding electrode conductor and the equipment grounding conductor are sized from two different tables against two different inputs, and the ground rod exception quietly caps one of them. Read what the conductor connects to before you read any table.

Worked example

Take a service fed with 3/0 AWG copper service conductors and find the required copper grounding electrode conductor. Walk it the way you would on the exam, one step at a time.

  1. Identify the input. The largest ungrounded service-entrance conductor is 3/0 AWG copper. Table 250.66 is driven by that service conductor size, not by the load.
  2. Pick the row in Table 250.66.3/0 copper falls in the “2/0 or 3/0 copper” row of the table.
  3. Read the required conductor. That row calls for a 4 AWG copper grounding electrode conductor.
  4. Check the 250.66(A) exception. If this conductor runs only to a ground rod, it never has to be larger than 6 AWG copper, so the table result is capped down for that single-rod run.

The numbers you have to defend are the 4 AWG copper from the table and the 6 AWG copper cap from 250.66(A), plus the articles they come from. Once you know which row the service conductor lands in, the answer is read straight off Table 250.66, and the only judgment left is whether the ground rod exception applies.

Why this topic costs points

Grounding and bonding is open book, which is exactly why candidates lose points on it. Article 250 and its tables are sitting in front of you, so it feels safe, and that false sense of safety is the trap. Three things go wrong under the clock.

  • The wrong table. Candidates size the grounding electrode conductor off Table 250.122, the equipment grounding conductor table, or the reverse. Table 250.66 is keyed to the service conductor and 250.122 is keyed to the overcurrent device, so confirm which conductor the question wants before you open a table.
  • Missing the ground rod exception. Sizing straight off Table 250.66 oversizes the conductor to a single ground rod, because 250.66(A) caps that run at 6 AWG copper. The table gives one answer and the exception quietly overrides it.
  • The lookup eats the clock. The NEC and theory section is 60 questions in 3 hours. If you hunt through Article 250 on every grounding question, you bleed time you needed for conduit fill, motor, and dwelling load problems later in the section.

That is why drilling grounding and bonding is not about memorizing one answer. It is about making the read automatic: identify the conductor, pick the right table, check the exception, so the only time you spend in the book is the row you already know you need.

Practice it inside the Washington bank

Reading the rule is not the same as drilling it under time. The free 15-minute Washington diagnostic scores you against the NEC and theory section and the Washington Laws and Rules section separately, so you see whether topics like grounding and bonding are actually what is costing you points, or whether your weak spot is somewhere else. From there you drill the section that is dragging your score instead of grinding everything evenly. We will not quote you a grounding and bonding question count we have not verified. We will route you to the diagnostic and the practice platform so you can rehearse the topic and the table lookup the way the exam asks for it.

Where these exam facts come from: L&I Electrical Examination Information, L&I Electrician Licensing & Requirements, WAC 296-46B (Washington electrical code adoption). The grounding electrode conductor sizing comes from NEC Table 250.66 and 250.66(A), paraphrased here, never reproduced.

See if grounding and bonding is really your weak spot

Knowing the rule is step one. Step two is finding out where you actually stand. The free 15-minute diagnostic scores the NEC and theory section and the Washington Laws and Rules section separately, so you drill the topics costing you points instead of guessing.

Take the free Washington diagnostic
Related reading