JourneymanIQ
NEC Calculations

NEC Article 220: Dwelling Unit Load Calculations (Standard and Optional Methods)

A dwelling load calculation is one of the heaviest-weighted calculation questions on the journeyman exam, and it is where most candidates leak points. The math is not hard. The bookkeeping is. You have to know which loads go in at full value, which loads get a demand factor, which table to open for the range, and which method the question is even asking for. Get those four things straight and the rest is arithmetic. This guide walks both the standard method and the 220.82 optional method for the same house, end to end, so you can see why they land on different numbers and when each one applies.

Last reviewed June 2026

What Article 220 actually asks you to do

Article 220 tells you how to add up the loads on a dwelling service or feeder so you can size the service-entrance conductors and the panel. The point of the article is demand factors. A house has a stove, a dryer, a water heater, lighting, and a dozen receptacle circuits, but the homeowner never runs all of them at full power at the same moment. So the code lets you discount certain loads instead of adding everything at 100 percent. Knowing which loads get discounted, and by how much, is the whole game.

There are two legal ways to do a single-family dwelling: the standard method in Part III of Article 220, and the optional method in 220.82. They are both correct. They usually land within a few amps of each other. The exam will tell you, directly or through the values it gives you, which one it wants.

Standard method, step by step

The standard method (Article 220 Part III) builds the load in pieces, applies a demand factor to each piece that allows one, then totals it. Here is the order I run it in every time.

  • General lighting and receptacle load: 3 VA per square foot of living area (Article 220). Garages, open porches, and unfinished spaces not adaptable for future use do not count.
  • Small-appliance branch circuits: two are required in a dwelling, counted at 1,500 VA each (220.52(A)).
  • Laundry branch circuit: one required, counted at 1,500 VA (220.52(B)).
  • Add those three pieces together, then apply the general demand factor: first 3,000 VA at 100 percent, the next 117,000 VA at 35 percent (the lighting demand-factor table in Article 220; the exact table number depends on your adopted edition).
  • Electric range: demand load from Table 220.55, not the nameplate.
  • Electric clothes dryer: the larger of 5,000 VA or the nameplate, then the demand from Table 220.54 (220.54).
  • Fixed (fastened-in-place) appliances: if there are four or more besides the range, dryer, space heating, and A/C, apply a 75 percent demand factor to that group (220.53).
  • Heating versus air conditioning: take the larger of the two and drop the smaller. They never run together (220.60).
  • Total it all in VA, divide by the service voltage (240 V for a 120/240 V single-phase service) to get amps.

Worked standard-method example

Take a 2,000 sq ft single-family dwelling on a 120/240 V single-phase service with a 12 kW electric range, a 5,000 VA electric dryer, 9 kW of electric heat, and a 4 kW (about 16.7 A at 240 V) central A/C. Here is the standard method run clean.

  • General lighting: 2,000 sq ft x 3 VA = 6,000 VA.
  • Small-appliance circuits: 2 x 1,500 = 3,000 VA. Laundry: 1,500 VA. Lighting + appliance + laundry subtotal = 6,000 + 3,000 + 1,500 = 10,500 VA.
  • Apply the general demand factor: first 3,000 VA at 100 percent = 3,000 VA. Remainder 10,500 - 3,000 = 7,500 VA at 35 percent = 2,625 VA. Demand subtotal = 3,000 + 2,625 = 5,625 VA.
  • Range: one 12 kW range, Column C of Table 220.55, demand = 8,000 VA.
  • Dryer: nameplate is 5,000 VA, which is also the 5,000 VA minimum, so 5,000 VA. One dryer at 100 percent per Table 220.54 = 5,000 VA.
  • Heat vs A/C: 9,000 VA heat versus 4,000 VA A/C. Take the larger: 9,000 VA. Drop the A/C.
  • Total: 5,625 + 8,000 + 5,000 + 9,000 = 27,625 VA.
  • Amps: 27,625 VA / 240 V = 115.1 A. That points to a 125 A service.

Optional method (220.82), step by step

The optional method in 220.82 is a shortcut that applies to a single dwelling unit served by a single 120/240 V or 120/208 V set of service or feeder conductors rated 100 A or larger. It splits the work into two buckets that get added at the very end.

  • Bucket one is the general load (220.82(B)): 3 VA per square foot for lighting, 1,500 VA for each of the two small-appliance circuits and the laundry circuit, the nameplate VA of every fastened-in-place, permanently connected, or fixed appliance, the nameplate of the range and dryer, and the nameplate of motors and low-power-factor loads. Add all of that connected load, then apply the demand: first 10,000 VA at 100 percent, everything over 10,000 VA at 40 percent.
  • Bucket two is heating and air conditioning (220.82(C)), and you take the largest single item from a short list: 100 percent of the A/C, 100 percent of a heat pump compressor, 65 percent of central electric space heating, 65 percent of electric heat with fewer than four separately controlled units, or 100 percent of heat with four or more separately controlled units. You pick the one that gives the largest number and use only that.
  • Add bucket one and bucket two, then divide by the service voltage for amps.

Same house, optional method

Run the same 2,000 sq ft house through 220.82 and watch the number move.

  • General load (nameplate, no per-appliance demand yet): lighting 6,000 + small-appliance 3,000 + laundry 1,500 + range 12,000 + dryer 5,000 = 27,500 VA.
  • Apply the 220.82(B) demand: first 10,000 VA at 100 percent = 10,000 VA. Remainder 27,500 - 10,000 = 17,500 VA at 40 percent = 7,000 VA. General load demand = 17,000 VA.
  • Heating/AC per 220.82(C): central electric heat 9,000 VA at 65 percent = 5,850 VA, versus A/C 4,000 VA at 100 percent = 4,000 VA. Take the larger: 5,850 VA.
  • Total: 17,000 + 5,850 = 22,850 VA.
  • Amps: 22,850 VA / 240 V = 95.2 A. That still points to a 100 A service, which is also the floor for using this method.

Notice the optional method came out lower here (95 A versus 115 A). That is normal. The optional method is more forgiving on the general load. On the exam, do not 'check your work' by running the other method and expecting a match. They are supposed to differ. Pick the method the question asks for and report that number.

The range table is its own trap

Table 220.55 has three columns and a fistful of notes, and the exam loves to make you use the wrong one. Column C is for ranges over 8.75 kW; for one range rated not over 12 kW, the answer is simply 8 kW of demand. If the range is over 12 kW you increase the Column C value by 5 percent for each additional kilowatt (or major fraction) above 12. For multiple ranges, smaller ranges, ovens and cooktops counted as units, or commercial cooking, you are into the notes and Columns A and B. Read the column headers before you read the numbers.

How this shows up on the exam

Dwelling load is one of the most reliable calculation questions on a journeyman exam. Expect a full multi-step problem that hands you a square footage, a range nameplate, a dryer, and a heat-versus-A/C pair, and asks for either total VA or the minimum service-conductor ampacity. The clean candidates lose points not on the arithmetic but on the setup.

You will also see smaller stand-alone questions that probe one piece: 'What is the general lighting load for a 2,400 sq ft dwelling?' (answer: 2,400 x 3 = 7,200 VA), or 'What demand is permitted for one 11 kW range?' (answer: 8 kW from Column C), or 'How many small-appliance circuits must be included and at what VA?' Drill the pieces and the full problems get easy.

Watch for the 83 percent service-conductor allowance in 310.12. For certain dwelling services and feeders that carry the entire load, the conductors may be sized at not less than 83 percent of the service rating. It is dwelling-specific and load-specific. Candidates misapply it to commercial feeders or to a feeder that does not carry the whole dwelling, and the exam writes wrong answers to catch exactly that.

The traps that cost points

  • Adding everything at 100 percent. The whole article is demand factors. If you skipped the first-3,000-at-100-then-35-percent step, you over-built the load and missed it.
  • Forgetting the small-appliance and laundry circuits. That is a required 4,500 VA (three circuits at 1,500 VA) that does not depend on square footage, and it is easy to leave out.
  • Using the range nameplate instead of Table 220.55. A 12 kW range is 8 kW of demand, not 12.
  • Pulling the wrong column of Table 220.55. Column C is the workhorse for a single ordinary range; the notes and Columns A and B are for special cases.
  • Adding heat and A/C together. They are noncoincident loads (220.60). Take the larger, drop the smaller.
  • Mixing the standard and optional methods. Pick one. The demand factors and their order are different, and a hybrid answer is wrong in both methods.
  • Forgetting the dryer 5,000 VA minimum. A 4,200 VA nameplate is still counted at 5,000 VA (220.54).

See where you stand on these calculations

The free 15-minute diagnostic scores your calculation areas separately and shows exactly which ones are costing you points, before you spend a dollar.

Related reading