Branch Circuits vs Feeders
The exam does not care that the wire looks the same in the pipe. It cares where the conductor sits relative to the final overcurrent device. Name that first and the article choice gets much cleaner.
Last reviewed July 2026
The one question to ask first
Ask this before the calculator comes out: where is the final overcurrent device protecting the load?
- After the final breaker or fuse: branch circuit.
- Before the final breaker or fuse: feeder.
- If the conductor supplies a panel that has the branch breakers, you are usually in feeder territory.
- If the conductor leaves the breaker and runs to receptacles, lighting, equipment, or one motor, you are usually in branch-circuit territory.
For the conductor-sizing rule itself, the dedicated NEC 210.19 branch-circuit guide goes deeper on continuous loads and termination limits.
Branch circuit worked example
A 277 V branch circuit feeds a 16 A continuous lighting load and a 6 A noncontinuous load. What minimum conductor ampacity does the sizing step require before selecting from the ampacity table?
- Name the conductor: branch circuit, because it is after the final breaker and feeds the loads.
- Use the continuous-load pattern: 125% of continuous load plus 100% of noncontinuous load.
- Continuous portion: 16 A x 1.25 = 20 A.
- Noncontinuous portion: 6 A.
- Minimum ampacity before conductor selection: 20 A + 6 A = 26 A.
Feeder worked example
A feeder supplies a small panel with 24 A of continuous load and 40 A of noncontinuous load after any allowed demand factors. What is the minimum feeder ampacity before conductor selection?
- Name the conductor: feeder, because it supplies the panel with the final branch-circuit breakers.
- Continuous portion: 24 A x 1.25 = 30 A.
- Noncontinuous portion: 40 A.
- Minimum feeder ampacity before conductor selection: 30 A + 40 A = 70 A.
- If the question is a dwelling feeder or service, check whether Article 220 demand factors or 310.12 apply before choosing the final conductor.
What changes between Article 210 and Article 215
- Article 210 owns branch-circuit requirements such as required circuits, outlet rules, and branch-circuit conductor sizing.
- Article 215 owns feeder requirements such as feeder conductor sizing, feeder overcurrent context, and feeder neutral rules.
- Article 220 often supplies the calculated load for either one.
- Article 310 still supplies ampacity and adjustment rules after you know the load.
Wrong answers the exam wants you to pick
Calling every panel conductor a branch circuit
The conductors feeding a panel are not branch circuits just because the panel has branch breakers inside it. They are feeders until those final breakers protect the load-side circuits.
Using demand factors on a simple branch circuit
Demand factors live in load calculations. A single branch circuit serving a known continuous load usually does not get a dwelling demand shortcut.
Forgetting the continuous-load step
The branch-versus-feeder decision does not remove the 125% step when the rule calls for it. Name the conductor, then size the load.
How to drill this for the exam
Draw one line on scratch paper: source, feeder, final breaker, branch circuit, load. Put the conductors from the problem on that line. Once the conductor has a name, the code article usually stops being a guessing game.
Find out whether feeder and branch-circuit questions are costing you
The free diagnostic separates branch circuits, feeders, load calculations, ampacity, and grounding so your next practice block has a target.