JourneymanIQ
California · topic

Branch Circuit Practice Questions for the California Exam

Branch circuit questions usually hinge on one word: continuous. Spot it and the 125% rule does the rest. Here is the rule, the trap, and an original question worked through.

Last reviewed June 2026

What the exam is really testing

  • Spotting a continuous load (three hours or more of operation).
  • The 125% rule for conductors and overcurrent devices, per 210.19 and 210.20.
  • Distinguishing a branch circuit (ends at the load) from a feeder (ends at another device).
  • Receptacle and lighting branch-circuit requirements.

The trap

Candidates size a continuous load at 100%. A 24-amp continuous load is not a 24-amp circuit, it is a 30-amp circuit. Miss the word continuous and you undersize.

Try an original question

Sample question · original

A continuous lighting load draws 24 amps.

Per NEC 210.19 and 210.20, what minimum branch-circuit conductor ampacity and overcurrent device rating are required?

  • A24 amps
  • B27 amps
  • 30 amps
  • D35 amps

Answer C. 210.19(A) and 210.20(A) require conductors and the overcurrent device to be rated at least 125% of a continuous load. 24 amps times 1.25 equals 30 amps.

  • NEC 2023 210.19(A)
  • NEC 2023 210.20(A)

Why the other answers tempt you

  • A: 24 amps ignores the continuous 125% requirement.
  • B: 27 amps is roughly 112.5%, which is not the rule.
  • D: 35 amps overshoots the 125% requirement.

Drill it on the platform

Find your path
Not sure it’s your only weak spot?

Check every domain in 15 minutes.

Drill this topic, then run the diagnostic to see if anything else is leaking points on the California General Electrician exam. Free, no signup.

Take the free diagnostic
Related reading