JourneymanIQ
Texas · calculations

TDLR voltage drop practice

Voltage drop is the voltage you lose pushing current down a long run of wire. Too much and motors run hot and lights dim. This is a TDLR Calculations-part question type, now scored on its own. Here is the pattern, one worked example, and an original question to try.

Last reviewed June 2026

One worked example

A 120-volt garage circuit feeds a 16-amp battery charger 70 feet from the panel on 12 AWG copper. Is the voltage drop a problem?

  1. 1
    Name the problem

    This is a single-phase voltage drop. The current runs out to the load and back, so the distance counts twice. That is where the 2 comes from.

  2. 2
    Pick the formula

    K is the resistance constant for the metal. I is the load current. D is the one-way distance. CM is the conductor area in circular mils.

    VD = (2 × K × I × D) / CM

  3. 3
    Pull the numbers

    Copper K is 12.9. Load is 16 A. One-way run is 70 ft. 12 AWG is 6,530 circular mils.

  4. 4
    Run the arithmetic

    Multiply across the top, then divide by the circular mils.

    VD = (2 × 12.9 × 16 × 70) / 6,530

    VD = 28,896 / 6,530

    VD = 4.43 V

  5. 5
    Check it against the supply

    4.43 V is 3.69% of 120 V. NEC recommends staying under 3% on a branch circuit. Above the 3% target for branches. Borderline. Check the application.

    4.43 / 120 = 3.69%

Try an original question

Sample question · original

A 240-volt single-phase circuit feeds a 20-amp load 100 feet away on 10 AWG copper. Copper's K is 12.9, and 10 AWG is 10,380 circular mils.

What is the approximate voltage drop?

  • A2.5 volts
  • 5.0 volts
  • C9.9 volts
  • D7.9 volts

Answer B. VD = (2 x K x I x L) / CM = (2 x 12.9 x 20 x 100) / 10,380 = 51,600 / 10,380, which is about 5.0 volts.

  • NEC 2023 Chapter 9, Table 8

Why the other answers tempt you

  • A: 2.5 volts forgets the 2 for the round trip. On single phase the current goes out and comes back, so the run counts twice.
  • C: 9.9 volts applies the round-trip factor twice. The 2 goes in once.
  • D: 7.9 volts uses 12 AWG circular mils (6,530) instead of 10 AWG (10,380). Smaller wire, bigger drop, wrong wire.

Train it, one step at a time

Find your path
Not sure it’s your only weak spot?

Check every domain in 15 minutes.

Drill this topic, then run the diagnostic to see if anything else is leaking points on the TDLR Journeyman exam. Free, no signup.

Take the free diagnostic
Related reading