NEC Table Lookup Practice for the California Electrician Exam
Most exam math ends in a table. The fast candidates read three columns without re-reading the question. The slow ones re-read the stem every time. Here is how to train the difference.
Last reviewed June 2026
What to train
- Table 310.16: pick the right temperature column before you read a row.
- Chapter 9 conduit fill: Table 1 for percent, Table 4 for conduit area, Table 5 for wire area.
- 314.16(B) box fill: count conductors, then read the volume allowance per size.
- Demand tables: 220.55 for ranges, 220.54 for dryers, 220.42 for lighting demand.
What slows candidates down
- Reading the 90C column when the terminals are only rated 75C.
- Forgetting conduit fill uses three different Chapter 9 tables, not one.
- Recounting box conductors mid-lookup because you lost your place.
- Hunting for a demand table without knowing its number.
Mini drill: find it fast
Close the book. Read each cue, say the index keyword you would search and the article out loud, then check yourself. If it takes more than fifteen seconds, that one goes on your tab list.
Ampacity of 3/0 copper THHN at the 75C terminal rating
Read the 75C copper column down to the 3/0 row.
Keyword: Ampacity, conductors
Table 310.16
Percent fill for three or more conductors in conduit
Over two conductors is a 40 percent fill limit.
Keyword: Conduit, fill
Chapter 9, Table 1
Usable area of 3/4 inch EMT
The 40 percent column gives the usable area.
Keyword: Conduit, dimensions
Chapter 9, Table 4
Volume allowance for one 12 AWG conductor
Cubic-inch allowance per conductor size.
Keyword: Box, fill
Table 314.16(B)
Demand for eight household electric ranges
Column C gives the demand in kW by count.
Keyword: Ranges, demand
Table 220.55
Train this against the clock
Check every domain in 15 minutes.
Drill this topic, then run the diagnostic to see if anything else is leaking points on the California General Electrician exam. Free, no signup.
Take the free diagnostic