TDLR motor calculation practice
Motor wiring sizes off the table full-load current, not the nameplate, and the conductor carries 125% of it. This is a TDLR Calculations-part question type, now scored on its own. Here is the pattern, one worked example, and an original question to try.
Last reviewed June 2026
One worked example
A 10 HP, 230-volt, three-phase motor. Table 430.250 gives a full-load current of 28 amps. Size the branch-circuit conductor.
- 1Name the problem
Single motor conductor. Use the table FLC and the 125% rule.
- 2Pick the rule
Branch-circuit conductors for a single motor carry 125% of the table full-load current (430.22).
Conductor = 1.25 × FLC
- 3Pull the numbers
Table FLC is 28 amps.
- 4Run the arithmetic
Add the 25%.
Conductor = 1.25 × 28 = 35 A
- 5Check it
35 amps. Size the wire for 35, even though the nameplate might read lower.
Try an original question
A 10 HP, 240-volt, single-phase motor. Table 430.248 gives a full-load current of 50 amps. Size the branch-circuit conductor.
What is the minimum conductor ampacity?
- A50 amps
- 62.5 amps
- C40 amps
- D70 amps
Answer B. 430.22 requires branch-circuit conductors for a single motor to be 125% of the table full-load current. 1.25 x 50 = 62.5 amps. Use the table FLC, never the nameplate.
- NEC 2023 430.22
- NEC 2023 Table 430.248
Why the other answers tempt you
- A: 50 amps is the table value with no 125%. A single-motor conductor carries 125% of the full-load current.
- C: 40 amps applies an 80% derate instead of the 125% increase. Motor conductors go up, not down.
- D: 70 amps is the next standard breaker size, not the required conductor ampacity.
Train it, one step at a time
Check every domain in 15 minutes.
Drill this topic, then run the diagnostic to see if anything else is leaking points on the TDLR Journeyman exam. Free, no signup.
Take the free diagnostic