JourneymanIQ
California · topic

Motor Calculations Practice for the California Exam

Motor wiring sizes off the table full-load current, not the nameplate, and the conductor carries 125% of it. On the California exam, calculations are part of the Determination of electrical system requirements domain. Here is the pattern, one worked example, and a question to try.

Last reviewed June 2026

One worked example

A 10 HP, 230-volt, three-phase motor. Table 430.250 gives a full-load current of 28 amps. Size the branch-circuit conductor.

  1. 1
    Name the problem

    Single motor conductor. Use the table FLC and the 125% rule.

  2. 2
    Pick the rule

    Branch-circuit conductors for a single motor carry 125% of the table full-load current (430.22).

    Conductor = 1.25 × FLC

  3. 3
    Pull the numbers

    Table FLC is 28 amps.

  4. 4
    Run the arithmetic

    Add the 25%.

    Conductor = 1.25 × 28 = 35 A

  5. 5
    Check it

    35 amps. Size the wire for 35, even though the nameplate might read lower.

Now try one

Your turn. A 5 HP, 230-volt, three-phase motor. Table 430.250 gives a full-load current of 15.2 amps.

What's the minimum conductor ampacity at 125%, in amps?

  1. 1
    Run the arithmetic

    Add the 25%.

    Conductor = 1.25 × 15.2 = 19 A

  2. 2
    Check it

    19 amps. Off the table value, always, not the motor's nameplate amps.

Train it on the platform

Find your path
Not sure it’s your only weak spot?

Check every domain in 15 minutes.

Drill this topic, then run the diagnostic to see if anything else is leaking points on the California General Electrician exam. Free, no signup.

Take the free diagnostic
Related reading