Motor Calculations Practice for the California Exam
Motor wiring sizes off the table full-load current, not the nameplate, and the conductor carries 125% of it. On the California exam, calculations are part of the Determination of electrical system requirements domain. Here is the pattern, one worked example, and a question to try.
Last reviewed June 2026
One worked example
A 10 HP, 230-volt, three-phase motor. Table 430.250 gives a full-load current of 28 amps. Size the branch-circuit conductor.
- 1Name the problem
Single motor conductor. Use the table FLC and the 125% rule.
- 2Pick the rule
Branch-circuit conductors for a single motor carry 125% of the table full-load current (430.22).
Conductor = 1.25 × FLC
- 3Pull the numbers
Table FLC is 28 amps.
- 4Run the arithmetic
Add the 25%.
Conductor = 1.25 × 28 = 35 A
- 5Check it
35 amps. Size the wire for 35, even though the nameplate might read lower.
Now try one
Your turn. A 5 HP, 230-volt, three-phase motor. Table 430.250 gives a full-load current of 15.2 amps.
What's the minimum conductor ampacity at 125%, in amps?
- 1Run the arithmetic
Add the 25%.
Conductor = 1.25 × 15.2 = 19 A
- 2Check it
19 amps. Off the table value, always, not the motor's nameplate amps.
Train it on the platform
Check every domain in 15 minutes.
Drill this topic, then run the diagnostic to see if anything else is leaking points on the California General Electrician exam. Free, no signup.
Take the free diagnostic