JourneymanIQ
Calculator | NEC 310.16

Ampacity calculator.

Calculate adjusted conductor ampacity for common exam setups. Pick the conductor, table column, terminal rating, current-carrying conductor count, and ambient temperature.

This calculator covers the normal Table 310.16 adjustment path. It does not size the overcurrent device or apply every equipment exception.

Direct answer: start with the Table 310.16 ampacity for the conductor and insulation column, multiply by the ambient correction factor, multiply by the current-carrying conductor adjustment factor, then cap the result at the terminal temperature rating.

Conductor material
Insulation column
Terminal rating
Assignable ampacity99.84 A
Adjusted ampacity99.84 A
Terminal cap115 A

The adjusted ampacity is below the terminal cap, so the derated value controls. This is not the breaker size.

Worked example

2 AWG copper THHN, six current-carrying conductors, 35 C ambient

Inputs

  • 2 AWG copper
  • 90 C insulation column
  • 75 C terminals
  • Six current-carrying conductors
  • 35 C ambient temperature

Result

Base ampacity is 130 A. Ambient correction is 0.96. Six current-carrying conductors use the 0.80 adjustment factor. Final adjusted ampacity is 99.84 A, below the 75 C terminal cap of 115 A.

Here is the trap: the 90 C column can help with derating math, but it does not let you ignore the terminal rating. Always compare the adjusted value to the terminal cap.

Common misses

Ampacity mistakes that show up on exam questions

Related practice

After the ampacity math, drill the table

FAQ

Ampacity calculator questions

What does this ampacity calculator do?

It starts with a Table 310.16 conductor ampacity, applies ambient temperature correction, applies the current-carrying conductor adjustment factor, then compares the result to the terminal temperature limit.

Does the equipment grounding conductor count as current carrying?

No. For the common adjustment-factor setup, the equipment grounding conductor is not counted as a current-carrying conductor. Neutrals depend on the circuit, so read the question carefully.

Why can I start in the 90 C column if my terminals are 75 C?

Many exam questions let you use the insulation column for correction and adjustment, then cap the final assignable ampacity at the terminal rating. The terminal cap still has to be checked.

Is the ampacity result the breaker size?

No. The result is assignable conductor ampacity. Breaker sizing depends on load type, standard OCPD sizes, small-conductor rules, motor rules, equipment instructions, and the exact code article in the question.

Which NEC sections are involved?

The common exam path is Table 310.16 for base ampacity, 310.15 for ambient correction and conductor adjustment, and 110.14(C) for terminal temperature limits.

While you’re here

See where you actually stand on the exam.

15 questions. 15 minutes. No signup. You get a topic-by-topic weakness map showing exactly which NEC sections to focus on before test day.

Take the free diagnostic