JourneymanIQ
Article 430 · NEC Table 430.250 deep-dive

NEC Table 430.250: Three-Phase Motor FLC for Branch Circuit Sizing

Article 430 motor questions are 8-12% of every TDLR Journeyman and California General Electrician exam. Table 430.250 is the table that drives most of them. The single most common motor-question trap: mixing Table 430.250 FLC with motor nameplate FLA. Here's the table, the rule that uses it, and the trap to avoid.

Last reviewed May 2026

FLC vs FLA — the distinction that decides most motor questions

  • FLC (Full Load Current): from NEC Tables 430.247 (DC), 430.248 (single-phase AC), 430.249 (two-phase), or 430.250 (three-phase). Used for: branch circuit conductor sizing (430.22) and short-circuit/ground-fault protection (430.52).
  • FLA (Full Load Amps): from the motor nameplate. Used for: overload protection (430.32) and motor controller sizing.

NEC Table 430.250 values (three-phase motors)

The most common voltages on the exam are 230V (residential and light commercial three-phase), 460V (commercial and industrial), and 575V (some industrial). The table also covers 200V, 208V, 2300V, 4000V — verify the column you need on the exam.

HP230V FLC460V FLC575V FLC
1/22.2 A1.1 A0.9 A
3/43.2 A1.6 A1.3 A
14.2 A2.1 A1.7 A
1-1/26.0 A3.0 A2.4 A
26.8 A3.4 A2.7 A
39.6 A4.8 A3.9 A
515.2 A7.6 A6.1 A
7-1/222 A11 A9 A
1028 A14 A11 A
1542 A21 A17 A
2054 A27 A22 A
2568 A34 A27 A
3080 A40 A32 A
40104 A52 A41 A
50130 A65 A52 A
60154 A77 A62 A
75192 A96 A77 A
100248 A124 A99 A
125312 A156 A125 A
150360 A180 A144 A
200480 A240 A192 A

Memorize the 460V column for the most common commercial motors (10 HP through 50 HP). Most exam questions will reference 460V three-phase motors in this HP range.

NEC 430.22 — Branch circuit conductor sizing

For a single continuous-duty motor, branch circuit conductors must have an ampacity of at least 125% of the FLC from Table 430.247-250.

Formula: Required conductor ampacity ≥ FLC × 1.25

Worked example: 25 HP, 460V three-phase motor

  1. Look up FLC: Table 430.250, 25 HP, 460V column → 34 A
  2. Apply 125%: 34 × 1.25 = 42.5 A
  3. Required conductor ampacity: at least 42.5 A
  4. Look up conductor size in Table 310.16 (75°C column for typical equipment): 6 AWG copper = 65 A, 8 AWG copper = 50 A
  5. Smallest conductor with ≥ 42.5 A ampacity at 75°C: 8 AWG copper
  6. Final answer: 8 AWG copper minimum

NEC Table 430.52 — Short-circuit / ground-fault protection

Per 430.52, the OCPD protecting the motor branch circuit (as protection against short circuits and ground faults, NOT against overload) is sized as a percentage of FLC. Table 430.52 gives the maximum percentages, varying by motor type and protection device.

For a typical three-phase squirrel-cage motor with Code letters B-E or no Code letter:

  • Inverse-time circuit breaker: 250% of FLC
  • Non-time-delay (instantaneous-trip-only) fuse: 300% of FLC
  • Time-delay (dual-element) fuse: 175% of FLC
  • Instantaneous-trip breaker: 800% of FLC (with engineering supervision)

Worked example: SCGF for 25 HP, 460V motor with inverse-time breaker

  1. FLC: 34 A (Table 430.250)
  2. Apply 250% per Table 430.52: 34 × 2.5 = 85 A
  3. Standard breaker sizes per 240.6(A): 80 A, 90 A, 100 A...
  4. Per 430.52(C)(1) Exception 1, next standard size up is permitted if 250% doesn't equal a standard rating
  5. Final answer: 90 A inverse-time circuit breaker

How motor sizing questions appear on the exam

Question type 1: Direct conductor sizing (430.22)

“A continuous-duty 30 HP, 460V three-phase squirrel-cage motor. What is the minimum branch circuit conductor ampacity?” Answer: 40 A FLC × 1.25 = 50 A required ampacity.

Question type 2: SCGF sizing (430.52)

“Same motor with time-delay fuse protection. What is the maximum fuse size?” Answer: 40 A FLC × 1.75 = 70 A. Standard fuse size 70 A.

Question type 3: FLC vs FLA discrimination

“A 25 HP, 460V motor has nameplate FLA of 31 A. What is the minimum branch circuit conductor ampacity per 430.22?” Trap: candidates use 31 A nameplate. Correct answer uses Table 430.250 FLC of 34 A. Result: 34 × 1.25 = 42.5 A, NOT 31 × 1.25 = 38.75 A.

Question type 4: Overload (430.32) — uses nameplate, NOT FLC

“Same motor with nameplate FLA of 31 A and service factor 1.15. What is the maximum overload setting per 430.32(A)(1)?” Answer: 31 × 1.25 = 38.75 A. THIS time we use the nameplate FLA, not the table FLC. Same motor, two different numbers, two different sizing decisions.

Common 430.250 mistakes

  • Using nameplate FLA when 430.22 calls for FLC from Table 430.250
  • Reading the 230V column for a 460V motor (or vice versa) — common copy-paste error on multi-part questions
  • Forgetting that 430.22 requires 125% of FLC, not 100%
  • Using inverse-time breaker percentages (250%) when the question specifies time-delay fuse (175%)
  • Forgetting the “next standard size up” allowance per 430.52(C)(1) Exception 1 when the calculated value doesn’t match a standard rating
  • Mixing single-phase Table 430.248 with three-phase Table 430.250 — different tables for different motor types

Drill motor sizing across all four sizing decisions

The diagnostic includes motor problems for branch circuit, overload, SCGF, and feeder. Many candidates get one right and miss the other three because they mix FLC with FLA.

Related reading