JourneymanIQ
Article 250 · grounding electrode system

Article 250 Grounding Electrode System: A Visual Guide

The grounding electrode system is everything between the service neutral and earth. NEC 250.52 lists six types of permitted electrodes. 250.50 says use all of them that are present. 250.66 sizes the GEC. Three rules, one system.

Last reviewed May 2026

The six grounding electrode types (250.52)

  • Metal underground water pipe in direct contact with earth for 10 ft or more (250.52(A)(1)). Must be supplemented by another electrode.
  • Metal in-ground support structure (250.52(A)(2)). Building steel that’s buried.
  • Concrete-encased electrode (Ufer) (250.52(A)(3)). Bare copper or rebar in the foundation footing.
  • Ground ring (250.52(A)(4)). 20 ft or more of bare 2 AWG copper buried 2.5 ft or more.
  • Rod and pipe electrodes (250.52(A)(5)). 5/8 in × 8 ft, 90% bonded to earth.
  • Plate electrodes (250.52(A)(7)). 2 sq ft of metal surface, buried 2.5 ft or more.

The "use all that are present" rule (250.50)

If a building has more than one electrode type from 250.52(A)(1) through (A)(7), all of them must be bonded together. You don’t pick one. You bond them all to form a single grounding electrode system. If none of those exist, you must install one or more from 250.52(A)(4) through (A)(8).

Practical example: A new building with a metal water service, building steel, and a concrete-encased electrode requires all three to be bonded. A residential remodel with no Ufer and no building steel requires a rod or pipe electrode to be installed.

GEC sizing (Table 250.66)

The GEC connects the system to the electrode. Table 250.66 sizes it based on the largest ungrounded service conductor:

  • 2 AWG copper or smaller service → 8 AWG GEC
  • 1 AWG or 1/0 → 6 AWG
  • 2/0 or 3/0 → 4 AWG
  • Over 3/0 to 350 kcmil → 2 AWG
  • Over 350 to 600 kcmil → 1/0
  • Over 600 to 1100 kcmil → 2/0
  • Over 1100 kcmil → 3/0

The electrode-type caps

Table 250.66 references three caps for specific electrode types that override the table:

  • For rod, pipe, or plate electrodes (250.52(A)(5), (A)(7)): GEC need not exceed 6 AWG copper.
  • For concrete-encased electrode (250.52(A)(3)): GEC need not exceed 4 AWG copper.
  • For ground ring (250.52(A)(4)): GEC need not be larger than the ring conductor itself.

These caps catch candidates. The full Table 250.66 might say "2/0 copper" but if the only electrode is a rod, the GEC to that rod need only be 6 AWG.

Rod electrode resistance (250.53)

A single rod or pipe electrode that doesn’t achieve 25 ohms or less must be supplemented by an additional electrode at least 6 ft away. In practice, most installers default to two rods because measuring resistance takes special equipment.

Common exam patterns

  • List a service size, ask for GEC size to a specific electrode type. Trap: applying full table value when a cap applies.
  • Describe a building with multiple electrodes, ask "which one do you bond." Answer: all of them per 250.50.
  • Specify a single rod and ask for the next required action. Answer: measure resistance or add a second rod.
  • Single buried metal water pipe. Trap: need a supplemental electrode per 250.53(D)(2).

Drill Article 250 questions

The diagnostic includes grounding electrode system questions across all six electrode types and sizing scenarios.

Related reading